Sewage Flow Meter

2019-12-12 17:33:12

Sewage Flow Meter

General principles for electromagnetic flowmeter selection
(1) Whether the medium to be tested is a conductive liquid or slurry, thereby determining whether an electromagnetic flow meter is selected;
(2) The conductivity of the measured medium determines the type of electromagnetic flowmeter—whether it is high conductivity or low conductivity;
(3) The nominal diameter of the large, small and common flow process pipelines required by the process, determine whether the flow rate of the medium is at a more economical flow point, whether the pipeline needs to be reduced, and then determine the diameter of the flowmeter;
(4) Determine whether to use an integrated or split flowmeter, and the degree of protection of the flowmeter, etc., based on the layout of the process piping.
(5) Selecting the electrode type according to whether the measured medium is easy to crystallize or crusting;
(6) selecting an electrode material according to the corrosiveness of the measured medium;
(7) The corrosiveness, wear and temperature of the measured medium determine the lining material to be used;
(8) The high working pressure of the measured medium determines the nominal pressure of the flow meter;
(9) The insulation of the process piping determines the type of grounding ring.

Sewage Flow Meter

Turbine flowmeter composition
Turbine flowmeters are speed flowmeters, also known as impeller flowmeters. The impeller type flowmeter utilizes the relationship between the rotational angular velocity of the impeller placed in the fluid and the fluid flow velocity. By measuring the rotational speed of the impeller to reflect the volumetric flow rate of the fluid passing through the pipeline, it is a relatively mature high-accuracy instrument in the flowmeter. One. Turbine flowmeters generally consist of the following five typical parts:
1. Body
The material of the body is generally steel or cast iron, and the ends are flanged. The small diameter gauge also has a threaded interface.
2. Measured component
The turbine has precision machined blades that together with a set of reduction gears and bearings form the measuring assembly. The two high-precision stainless steel permanent self-lubricating bearings that support the turbine ensure a long service life of the assembly. Turbine flowmeters can also be lubricated with an external lubricant pump, but be careful not to overdo it.
3. counter
The following important information is available on the counter panel:
(1) Maximum working temperature and pressure:
(2) Metering and minimum and maximum flow levels
(3) Product model and number
(4) Explosion-proof grades and signs
(5) The equivalent of the fluid corresponding to the low frequency or high frequency pulse and the wiring method.
4. Rectifier
The rectifier is used to keep the fluid flowing through the turbine flow meter in a regular state, thereby eliminating the disturbance and having an unaffected effect on the metering. High metering accuracy.
5. Magnetic coupling transmission device
The device separates the counter portion in the atmospheric environment from the gas being measured and transmits the rotation of the measuring assembly to the counter.

Sewage Flow Meter

Maintenance of the turbine flowmeter sensor section:
1. Before the sensor is installed, use the mouth to blow or hand the impeller to make it rotate quickly to see if there is any display. Install the sensor when there is display. If there is no display, check the relevant parts and troubleshoot.
2. When using, keep the measured medium clean and free of impurities such as fibers and particles.
3. When the turbine flow sensor starts to use, the sensor should be slowly filled with the medium, and then the outlet valve should be opened (the valve should be installed at the back end of the flowmeter). It is forbidden to be impacted by the high-speed fluid when the sensor is in the mediumless state.
4. The maintenance period of the turbine flow sensor is generally half a year. When cleaning and cleaning, please be careful not to damage the parts in the measuring chamber, especially the impeller. Please be optimistic about the positional relationship between the guide and the impeller during assembly.
5. When the turbine flow sensor is not in use, the internal medium should be cleaned, and after drying, a protective cover is added at both ends of the sensor to prevent dust from entering, and then stored in a dry place.
6. The filter used in the turbine flowmeter should be cleaned regularly. When not in use, the internal medium should be cleaned. As with the sensor, add a dust jacket and store it in a dry place.