The structure of the electromagnetic flowmeter is mainly composed of a magnetic circuit system, a measuring conduit, an electrode, a casing, a lining, and a converter.
Magnetic circuit system: its role is to produce a uniform DC or AC magnetic field. The DC magnetic circuit is realized by a permanent magnet, which has the advantages of simple structure and less interference by the alternating magnetic field, but it is easy to polarize the electrolyte liquid in the measuring duct, so that the positive electrode is surrounded by negative ions, and the negative electrode is positive ion Surrounding, that is, the polarization phenomenon of the electrode, and causing an increase in internal resistance between the two electrodes, thus seriously affecting the normal operation of the meter. When the diameter of the pipe is large, the permanent magnets are correspondingly large, bulky and uneconomical, so the electromagnetic flowmeter generally adopts an alternating magnetic field and is generated by the excitation of a 50HZ power frequency power source.
Measuring catheter: its function is to let the conductive liquid to be tested pass. In order to make the magnetic flux diverted or short-circuited when the magnetic flux passes through the measuring catheter, the measuring catheter must be made of non-magnetic, low electrical conductivity, low thermal conductivity and mechanical strength. Non-magnetic stainless steel, FRP, high strength can be used. Plastic, aluminum, etc.

water flow indicator

Ultrasonic flowmeter performance characteristics
Measuring liquid: single fluid such as water, seawater, alkali, etc., turbidity less than 10000ppm, particle size less than 1mm
Pipe material: Ultrasonic penetrating full pipe such as steel, cast iron, PVC pipe, dense texture, no serious corrosion and scaling, allowing thin layer of dense lining
Pipe lining material: rubber, epoxy asphalt, fiberglass, mortar, etc., or unlined
Pipe diameter range: DN15mm~6000mm, plug-in sensor for pipe diameter DN25mm~6000mm
Flow rate range: -32m/s~0~+32m/s, bidirectional flow
Accuracy: ±1.0% of displayed value (under standard conditions). Configure plug-in sensor accuracy up to 0.5%
Linearity: 0.5%.
Signal output: 4-20mA or 0-20mA RS-485
Sensor: It is divided into external clip type and plug-in type. The standard configuration is clip-on. The maximum operating pressure of the plug-in sensor is 3 MPa.
Straight pipe length: upstream >10D, downstream >5D from pump outlet >30D (D: pipe diameter)
Display mode: 2*20 character LCD display with LED backlight
Protection level: IP65
Explosion-proof grade: ExdIIBT4
Fixed ultrasonic flowmeter power supply: AC110V, AC220V, DC8~36V or AC7~30V
Ambient temperature / humidity: Host -20 ° C ~ +80 ° C; sensor -20 ° C ~ +80 ° C or -20 ° C ~ +160 ° C optional, the sensor can be immersed in water, water depth less than 2m.

water flow indicator

Precautions before gas turbine flowmeter is enabled
Keywords: gas turbine flowmeter, Tianxin gas turbine flowmeter, gas gas turbine flowmeter
First, the precautions before the gas turbine flowmeter is enabled
In order to ensure trouble-free, safe start-up and commissioning of the ultrasonic flowmeter, the following pre-checks must be carried out:
1. Before starting the flowmeter officially, be sure to handle each leak point;
2. Check the power supply voltage on the terminal block and the corresponding positive and negative polarity;
3. Check the polarity of the frequency output lead connected to the RS485 converter;
4. Check whether the gas turbine flowmeter and temperature/pressure transmitter display are correct and reliable, including the installation direction and verticality of the flowmeter; the sealing performance of all joints;
5, wiring inspection: should be in accordance with the system wiring diagram provided by Jiangsu Tianxin Instrument Co., Ltd., check all wiring is correct.
Second, the gas turbine flowmeter projection operation steps
1. Open the bypass shut-off valve;
2. Open the flow upstream shutoff valve;
3. Slowly open the downstream shutoff valve of the flowmeter;
4. Slowly close the bypass shutoff valve.
Third, the gas turbine flowmeter stop table operation steps
1. Open the bypass shut-off valve;
2. Turn off the downstream shutoff valve of the flowmeter;
3. Close the flow upstream shutoff valve;
Fourth, gas turbine flowmeter use precautions
1. The newly installed or repaired pipeline must be purged. When purging the metering line, the flow meter must be removed and the corresponding short section replaced the flow meter for purging.
2. When the gas turbine flowmeter pipeline is put into production, it should be slowly boosted and gradually increase the flow rate. When the production is stopped, it should be slowly depressurized.
3. Check the sound of the gas turbine flowmeter or the vibration of the casing during operation to determine whether the turbine blades and bearings are working properly. At low flow rates, attention should be paid to the change in sound, and the vibration of the casing is observed at high flow rates.