Electromagnetic Flow Meter For Hci

2020-08-05 02:44:52

Electromagnetic Flow Meter For Hci

Vortex flowmeter installation requirements for straight pipe sections:

It is very important that the vortex flowmeter installation meets the requirements for straight pipe sections. Its detailed requirements are as follows:
The flowmeter has certain requirements on the upstream and downstream straight pipe sections at the installation point, otherwise it will affect the measurement accuracy.
If there is a tapered pipe upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 15D (D is the pipe diameter) upstream of the flowmeter, and a straight pipe section of not less than 5D in the downstream.
If there is a diverging pipe upstream of the installation point of the flowmeter, the upstream of the flowmeter shall have a straight pipe section of not less than 18D (D is the pipe diameter), and the downstream shall have a straight pipe section of not less than 5D.
If there is a 90° elbow or down joint upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 20D upstream of the flowmeter, and a straight pipe section of not less than 5D downstream.
If there is a 90° elbow on the same plane upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 25D upstream of the flowmeter, and a straight pipe section of not less than 5D downstream.
The flow regulating valve or pressure regulating valve should be installed as far as possible downstream of the flowmeter 5D. If it must be installed upstream of the flowmeter, the upstream of the flowmeter should have a straight pipe section of not less than 25D, and the downstream should have a straight pipe section of not less than 5D. .
If there is a piston type or plunger type pump in the upstream of the flow meter, a piston type or a Roots type fan and a compressor, the upstream of the flow meter should have a straight pipe section of not less than 25D, and the downstream should have a straight pipe section of not less than 5D.
Special attention: If the valve is installed near the upstream of the installation point of the vortex flowmeter, the valve is continuously opened and closed, which has a great influence on the service life of the flowmeter, and it is very easy to cause permanent damage to the flowmeter. The flowmeter should be avoided to be installed on the very long pipelines in overhead. After a long time, the leakage of the flowmeter can easily cause the leakage of the flowmeter to the flange. If it has to be installed, it must be in the upstream and downstream of the flowmeter. Pipe fastening devices are provided separately.

Electromagnetic Flow Meter For Hci

The main technical parameters of ultrasonic external clamp flowmeter:
Measurement accuracy: better than 1%
Repeatability: better than 0.2%
Measurement period: 500ms (2 times per second, 128 sets of data collected per cycle)
Working power: 220VAC/8~36VDC
Maximum flow rate: 64m / s (flow rate resolution 0.001m / s)
Display: 2 × 10 Chinese characters backlit LCD can display instantaneous flow and positive, negative, net cumulative flow, flow rate, etc.
Operation: 4×4 touch keyboard (F4 main unit magnetic 4 button) operation
Signal input: 3 channels of 4-20mA analog input, accuracy 0.1%, can input pressure, liquid level, temperature and other signals
2-way three-wire PT100 platinum resistor
Signal output: 1 isolated RS485 output
1 way 4-20mA or 0-20mA output
1 channel isolated OCT (programmable between pulse width 6~1000ms, default 200ms)
1 relay output (pulse width 200ms)
Data storage: Optional built-in data storage (SD card) can store time, instantaneous flow, accumulated flow, signal status, etc., through special software, can import data into computer for statistical and management
Communication protocol: MODBUS protocol, M-BUS protocol, FUJI extension protocol, and compatible with communication protocols of similar products of other domestic manufacturers
Other functions: automatic memory before 512 days, the first 128 months, the first 10 years of positive / negative / net cumulative flow
Automatically remember the first 30 times of power-on and power-off time and flow rate, and can realize automatic or manual addition of traffic, which can be read by MODBUS protocol.
Programmable batch (quantitative) controller, fault self-diagnosis function
Software upgrade via code file transmitted via E-mail
Protection level: sensor IP68, F4 host IP68, remaining host IP65
Explosion-proof grade: EXdIIBT4 (JN-100F2 type)

Electromagnetic Flow Meter For Hci

Turbine flow meter applications
Turbine flow meters are widely used in the following measurement objects: petroleum, organic liquids, inorganic liquids, liquefied gases, natural gas, gas and cryogenic fluids. In the transshipment and gathering stations of foreign liquefied petroleum gas, refined oil and light crude oil, the first and last stations of large crude oil transmission pipelines use it for trade settlement. In Europe and the United States, the turbine flowmeter is the natural gas meter next to the orifice flowmeter. In the Netherlands alone, more than 2,600 gas turbine flowmeters of various sizes and pressures from 0.8 MPa to 6.5 MPa are used on the natural gas pipeline. Has become an excellent natural gas flow meter. Although the excellent metering characteristics of the turbine flow meter are favored by people, the impression is that the moving parts are short in use time, and they are inevitable in the selection. After people's unremitting efforts, it should be said that the situation has changed a lot. As the most versatile flowmeter, the turbine flowmeter has been developed into a multi-variety, full-series, multi-size mass production scale.