Two Wire System Magnetic Flow Meter

2020-08-10 02:55:43

Two Wire System Magnetic Flow Meter

Vortex flowmeter analysis and solution

6. The connection problem between the secondary instrument and the subsequent instrument. Due to the problem of the subsequent instrument or the maintenance of the subsequent instrument, the mA output circuit of the secondary instrument is interrupted. For this type of secondary instrument, this part is mainly related to the problem 2. Especially for the subsequent recorders, in the case that the recorder cannot be repaired for a long time, it is necessary to pay attention to shorting the output of the secondary meter.
7. The circuit always has no indication due to the failure of the secondary instrument flat-axle cable. Due to long-term operation, coupled with the influence of dust, the flat-axle cable is faulty, and the problem can be solved by cleaning or replacing the flat-axis cable.
8. For the problem 7, the main problem is that the secondary instrument shows that the fixing screw of the meter head is loose, causing the head to sink, the pointer and the case friction are large, the movement is not working, and the problem is solved by adjusting the meter head and re-fixing.
9. Use environmental issues. In particular, the sensor part installed in the well is affected by the humidity of the environment, which causes the circuit board to be damp. This part is mainly related to questions 2 and 2. Through the corresponding technical improvement measures, the sensor part with large humidity is re-separated from the probe part and the conversion part, and the separate type sensor is used. Therefore, the working environment is good, and the instrument has been running well.
10. Due to the poor adjustment of the site, or due to the actual situation after the adjustment. Due to the on-site vibration and noise balance adjustment and sensitivity adjustment is not good. Or because of the re-allocation of the situation after a period of operation after the adjustment, causing the indication problem, this part of the reason is mainly related to questions 4 and 5. Use an oscilloscope, plus the combined process operation, and re-adjust.

Two Wire System Magnetic Flow Meter

Gas turbine flowmeter and screwing vortex flowmeter measurement difference
Keywords: gas turbine flowmeter, Tianxin gas turbine flowmeter, gas gas turbine flowmeter
First, the characteristics of gas turbine flowmeter and spiral vortex flowmeter
Gas turbine flowmeter and screwing vortex flowmeter are the main gas metering instruments in China. In foreign countries, almost no one uses gas to swirl into the vortex flow meter. At present, there are certain applications in the domestic vortex flowmeter. In terms of standard conditions. The international standard ISO9551 promulgated by the International Organization for Standardization and the international recommendations R6, R32 promulgated by the International Organization of Legal Metrology (OIML) have corresponding national standards and regulations in China and developed countries. The above documents guarantee the authority of gas turbine flowmeters in gas metering. Sex. Gas-introducing vortex flowmeters have not yet established relevant standards. It is difficult to guarantee the authority of the flow meter in gas metering. At present, in domestic flow meters for gas measurement, gas turbine flowmeters dominate, and the vortex flowmeters also have a certain market. The use of the two is similar, and users often have doubts about the choice of the two.

Two Wire System Magnetic Flow Meter

In the case of small flow metering, the film surface ratio is the largest, the Roots flowmeter is second, and the turbine flowmeter is the smallest. The initial flow performance of the volumetric flowmeter should be superior to the velocity flowmeter. For industrial and commercial users with large total gas consumption and low heat load for each gas, the volumetric flowmeter, ie, the membrane meter and the Roots flowmeter, should be preferred to meet the flowmeter requirements of a single burner when used alone. It can also meet the measurement requirements of the maximum flow rate when all burners are used at the same time.
    Not all industrial and commercial users can solve the measurement problem by selecting a volumetric flowmeter with a larger range. The volumetric ratio of the volumetric flowmeter is limited, and it is impossible to increase without limit. The selection of the flowmeter cannot be solved. This kind of user has a measurement problem. When the user only uses a single device for gas, or when operating at low flow rate, the initial flow rate and minimum flow rate of a single flow meter may not meet the minimum flow rate requirement. A single large flow meter cannot measure low gas consumption, which will result in Large supply and marketing differences.