Ultrasonic flowmeter common problems (1)
1. The ultrasonic flowmeter probe is used for a period of time, and irregular alarms may occur. This problem is more common when there are more impurities in the transport medium. Solution: Clean the probe regularly (recommended once a year).
2. When the ultrasonic flowmeter transport medium contains liquid impurities such as water, the flow metering tube is prone to effusion, and the freezing of the pressure tube may occur when the temperature is low, especially in the northern regions in winter. Solution: Purge or electrify the pressure tube
3, the ultrasonic flowmeter is very strict on the requirements of the pipeline, there can be no abnormal noise, otherwise it will affect the measurement error.
During the propagation of ultrasonic waves, their strength is attenuated due to obstruction or absorption by impurities in the medium and medium. Whether it is an ultrasonic flowmeter or an ultrasonic level gauge, there is a certain requirement for the received sound wave intensity, so various attenuations are suppressed.
4. What is the instantaneous flow fluctuation?
The signal strength is large, and the measured fluid fluctuation is large.
Solution: Adjust the probe position, improve the signal strength, and ensure the signal strength is stable. If the fluid fluctuation is large, the position is not good. Re-select the point to ensure the 5D working condition after the first 10D.

Pulse Output Flow Meter Sensor

Second, choose from the type of flow meter
    Various flow meters, such as volumetric flowmeters, speedmeters, and differential pressuremeters, have different characteristics. Different flowmeter types have different turndown ratios. The turbine flowmeter has a turndown ratio of 1:20 to 1:30, the Roots flowmeter has a turndown ratio of 1:20 to 1:160, and the film gauge has a turndown ratio of 1: 160 (The error characteristic curves of these three kinds of flow meters are shown in Figure 1), and the appropriate flow meter should be selected according to the actual situation.
    By comparing the error characteristics of the above flowmeters, it can be seen that the starting flow of the membrane meter and the Roots flowmeter is small, the initial flow of the turbine meter is relatively large, and the membrane surface exhibits a positive deviation in the small flow state. The Roots flowmeter exhibits a negative deviation. At low flow rates, the gas supply company is more willing to select a membrane meter for metering.

Pulse Output Flow Meter Sensor

Installation of plug-in electromagnetic flowmeter
The plug-in electromagnetic flowmeter sensor installation upstream straight pipe section is not less than 5D (D means pipe diameter), the downstream straight pipe section is not less than 2D:
1. Vertical installation. When the sensor is inserted into the pipeline, it should be less than 5° from the vertical diameter of the pipeline section. It is suitable for measuring the cleaning medium with small vibration of the pipeline.
2, inclined installation, the axis of the sensor and the axis of the pipe to be tested is 45 °, suitable for large pipe diameter and measuring the flow of liquid containing other impurities in the medium, the installation method is small, not suitable for entanglement.
There are two ways to insert the insertion point of the electromagnetic flowmeter sensor: one is inserted into the central axis of the pipe to be tested (ie 1/2 times the diameter of the pipe); the other is inserted into the inner wall of the pipe at 1/4 of the pipe.
Sensor installation:
1. Clean the welding slag and burrs of the base of the pipe to be tested.
2. Turn off the upstream flow control valve or use low pressure water supply.
3. Install the DN50 ball valve on the mounting base. Pay attention to the long cavity of the ball valve. Check whether the ball valve can be fully open and fully closed. Install the screw seat, compression nut and rubber sealing ring onto the ball valve and loosen the positioning nut. Insert the sensor into the rod through the ball valve and insert it into the pipe to be tested. At the same time, it should be noted that the direction of the sensor direction indicator rod should be consistent with the flow direction of the fluid. Ordering Information Please specify the name of the tested medium, working pressure, medium temperature, flow rate (flow rate) range, pipe diameter and the pipe network to be tested.